Description
PL 12-3 320XRT is a PrimeLine luminaire, length 1270 mm, power 63.5 W, Transparent diffuser. PrimeLine ATEX emergency luminaire for central battery systems. Backup power comes from a compatible central system, not from a battery inside the luminaire. Certification covers Zones 1, 2, 21 and 22. GRP body, PC diffuser, IP66/IP67. Version X: CBX module, 3-pole terminals. Confirm system compatibility before ordering.
Technical specification
| Ordering code | PL 12-3 320XRT |
|---|---|
| Dimensions L×D×H | 1270x173x107 |
| Power | 63.5 W |
| Luminous flux AC | 8305 lm |
| Luminous flux DC (emergency) | 8305 lm |
| Colour temperature | 4000 K |
| CRI | >80 |
| IP | IP66 / IP67 |
| IK | IK09 |
| Housing | GRP |
| Diffuser | Transparent (PC) |
| Cable glands | M20 — 1 gland on each side |
| Terminals | 3-pole |
| Through wiring | 2.5 mm² / 105°C insulation |
| Isolating switch | yes |
| Ambient temperature | -30°C…+50°C |
| ATEX / IECEx | Ex II 2G Ex db eb mb IIC T4 Gb – Ex II 2D Ex tb IIIC T70°C Db |
| Zone | 1 |
Code PL 12-3 320XRT means: 1270 mm, ~14 W LED module, 3-pole terminal, M20 (1 gland on each side), central battery with addressing (CBX / V-CG-S), with isolating switch, transparent diffuser.
Applications and limitations
- backup power from a central system — not from a battery inside the luminaire;
- version X (CBX): 3-pole terminals; confirm system compatibility;
- take photometric and Ex data from this SKU / nameplate — do not generalise the whole family;
- install per IEC 60079-14 and the instruction for the exact version (S/B, 1/3 or X/Y);
- final selection must be made by a competent person for the installation.
Documents
- ATEX certificate KSCP 25ATEX0029X
- IECEx certificate KSCP 25.0045X
- EU Declaration of Conformity — PrimeLine
- PrimeLine data sheet
- Operating instruction (SKU version)
- Photometry package
- CNBOP certificate 6090/2026
FAQ
Does this luminaire have ATEX and IECEx certificates?
Yes. PrimeLine is covered by ATEX KSCP 25ATEX0029X and IECEx KSCP 25.0045X. Take the full Ex marking and temperature from the nameplate / this SKU.
Which zones is it intended for?
Certification covers gas Zones 1 and 2 and dust Zones 21 and 22. In the shop the Zone attribute for PrimeLine is 1. Final selection depends on the installation documents.
What is the ambient temperature range?
For PL 12-3 320XRT: -30°C…+50°C. HT/LT suffixes change the range — always confirm in the product code.
Does the luminaire include its own battery?
No. Backup power comes from a central system. Confirm CBX/CBY/B compatibility before ordering.
How does general lighting differ from emergency variants?
Code S = general. Codes 1/3 = internal battery (1.5 h / 3 h). Codes B/X/Y = central battery. These are separate SKUs and category children.
What luminous flux and power does PL 12-3 320XRT have?
PL 12-3 320XRT: 63.5 W, mains luminous flux 8305 lm, emergency mode 8305 lm. Wide symmetric distribution of approx. 115°. For lighting design (e.g. DIALux) use the photometric file of this code under Documents.
How many cable glands and stopping plugs does this luminaire need?
The luminaire has 2 M20 entries (1 gland on each side). Each needs a certified Ex cable gland matched to the cable diameter, and an unused one a certified stopping plug; an ordinary gland or plug breaches the luminaire certificate. Ex glands and stopping plugs are in the AtexBox gland accessories category.
Can supply be looped through this luminaire?
Yes. Glands at both ends allow supply to be looped through consecutive luminaires (through-wiring), reducing junction boxes.
Does this luminaire have an isolating switch, and what is its Ex marking?
Yes. The isolating switch disconnects power when the diffuser is opened; hence the gas marking II 2G Ex db eb mb IIC T4 Gb.
Which central battery system does it work with?
With a monitored EATON central battery — the addressable EATON V-CG-S module lets the central unit supervise each luminaire.
How is it built, and where is it used?
GRP body, UV-stabilised polycarbonate diffuser, IK09, IP66/IP67; the diffuser and LED plate are hinged, so nothing has to be set aside when opening. Ambient temperature for this code: -30°C…+50°C. Typical locations: loading ramps, unheated warehouses, cold stores (with the version matched to temperature) and chemical and petrochemical plants.
Where can I download the certificate and instructions?
See Documents on this page: ATEX, IECEx, EU declaration, data sheet, version-specific instruction and photometry.
Other PrimeLine lengths / powers — Central battery CBX · Transparent diffuser
Same function subcategory and the same terminals, gland layout and diffuser. Length and LED module vary. The current SKU is highlighted.
| SKU | Length | Module | Power | Flux AC |
|---|---|---|---|---|
PL 60-1 320XRT |
670 mm | 1 | 24.6 W | 2946 lm |
PL 60-2 320XRT |
670 mm | 2 | 29.4 W | 3613 lm |
PL 60-3 320XRT |
670 mm | 3 | 33.5 W | 4185 lm |
PL 12-1 320XRT |
1270 mm | 1 | 44.2 W | 5979 lm |
PL 12-2 320XRT |
1270 mm | 2 | 54.0 W | 7293 lm |
PL 12-3 320XRT |
1270 mm | 3 | 63.5 W | 8305 lm |






Reviews