Description
HSP1P 32 AC250 5P W-SCT is a HARDO HSP1P wall socket for Ex zones 1, 2, 21, 22. 32 A, voltage 200–250 V AC (Blue), poles 5P, PE h9. BMC (GRP) housing, IP66, Ex db eb / Ex tb. Certificate TÜV CY 25 ATEX 0207475 X. Use an HSP1P plug only with an HSP1P socket.
Code HSP1P 32 AC250 5P W-SCT means: Wall socket · 32 A · 200–250 V AC · 5P · PE h9.
Technical specification
| SKU | HSP1P 32 AC250 5P W-SCT |
|---|---|
| Type | Wall socket |
| Code D | W-SCT |
| Current | 32 A |
| Voltage | 200–250 V AC (Blue) |
| Poles | 5P (3P + N + PE) |
| PE position | h9 |
| Switching | Plug rotation |
| AUX contact | None |
| Cable / entry | M40 · 17–28 MM |
| Material | BMC (GRP) |
| Ex marking | II 2G Ex db eb IIC T6…T4 Gb; II 2D Ex tb IIIC T80°C Db |
| Zones | 1, 2, 21, 22 |
| IP | IP66 |
| Temperature | -45°C … +50°C |
| T class | T5 |
| ATEX certificate | TÜV CY 25 ATEX 0207475 X |
Limitations
Install and operate only per the HSP1P instruction and IEC 60079-14. A matching socket–plug pair needs the same current, voltage, poles and PE clock. Do not mix with other Ex socket series.
Documents
- HSP1P EU Declaration of Conformity
- HSP1P use and maintenance instruction
- Sockets and plugs catalogue
FAQ
What certificate covers HSP1P?
ATEX TÜV CY 25 ATEX 0207475 X. Marking: II 2G Ex db eb IIC T6…T4 Gb; II 2D Ex tb IIIC T80°C Db.
How do I match a socket and plug?
Same current, voltage, poles and PE clock. Only device type D differs (W-SCT / C-SCT / PLG).
Can an HSP1P plug be used with another Ex socket brand?
No. Use an HSP1P plug only with an HSP1P socket (mechanical interlock and coding).
What does HSP1P 32 AC250 5P W-SCT mate with?
Matches: HSP1P 32 AC250 5P PLG, HSP1P 32 AC250 5P C-SCT. Current (32 A), voltage, poles (5P) and PE position (h9) must be identical. Other combinations do not fit mechanically.
What does PE h9 mean?
Position of the protective earth contact on a clock face (IEC 60309), viewed from the socket front. h9 means 9 o'clock. A plug only fits a socket with the same PE position, which prevents voltage mix-ups.
What does 5P mean?
5P (3P + N + PE). 5P needs separate N and PE conductors (TN-S). PEN is split in the distribution board, not in the socket.
Which cable and cross-section?
Cable outer diameter: M40 · 17–28 mm (entry range). Conductor size is set by the designer or electrician: current-carrying capacity (IEC 60364-5-52), voltage drop over the route length and automatic disconnection; in Ex areas also IEC 60079-14.
Motor runs the wrong way — what to change?
Swap any two phases (e.g. L1 and L2) with the supply isolated, in the feeder or at the load. Done by an electrician; open Ex enclosures only per the HSP1P instruction.
Why can a connector overheat?
Usually loose terminals (torque per instruction), undersized conductors or worn contacts. The HSP1P interlock prevents withdrawal under load. Replace an overheated connector; periodic inspection per IEC 60079-17.
Where are the documents?
HSP1P documents: EU declaration, use and maintenance instruction, catalogue.
Matching HSP1P set — 32 A · 200~250V AC · 5P · PE h9
Matching wall / plug (and coupler when available) share current, voltage, poles, PE and AUX. The current SKU is highlighted.
| Type | SKU | Current | Voltage | Poles | PE | AUX |
|---|---|---|---|---|---|---|
| Wall socket | HSP1P 32 AC250 5P W-SCT |
32 A | 200~250V AC | 5P | h9 | None |
| Coupler socket | HSP1P 32 AC250 5P C-SCT |
32 A | 200~250V AC | 5P | h9 | None |
| Plug | HSP1P 32 AC250 5P PLG |
32 A | 200~250V AC | 5P | h9 | None |