Description
HSP1P 16 DC50 2P PLG is a HARDO HSP1P plug for Ex zones 1, 2, 21, 22. 16 A, voltage 36–50 V DC (White), poles 2P, PE n/a. PA66 housing, IP66, Ex db eb / Ex tb. Certificate TÜV CY 25 ATEX 0207475 X. Use an HSP1P plug only with an HSP1P socket.
Code HSP1P 16 DC50 2P PLG means: Plug · 16 A · 36–50 V DC · 2P · PE n/a.
Technical specification
| SKU | HSP1P 16 DC50 2P PLG |
|---|---|
| Type | Plug |
| Code D | PLG |
| Current | 16 A |
| Voltage | 36–50 V DC (White) |
| Poles | 2P |
| PE position | n/a |
| Switching | n/a |
| AUX contact | None |
| Cable / entry | M25 · 12.5–17 MM |
| Material | PA66 |
| Ex marking | II 2G Ex db eb IIC T6…T4 Gb; II 2D Ex tb IIIC T80°C Db |
| Zones | 1, 2, 21, 22 |
| IP | IP66 |
| Temperature | -45°C … +60°C |
| T class | T5 |
| ATEX certificate | TÜV CY 25 ATEX 0207475 X |
Limitations
Install and operate only per the HSP1P instruction and IEC 60079-14. A matching socket–plug pair needs the same current, voltage, poles and PE clock. Do not mix with other Ex socket series.
Documents
- HSP1P EU Declaration of Conformity
- HSP1P use and maintenance instruction
- Sockets and plugs catalogue
FAQ
What certificate covers HSP1P?
ATEX TÜV CY 25 ATEX 0207475 X. Marking: II 2G Ex db eb IIC T6…T4 Gb; II 2D Ex tb IIIC T80°C Db.
How do I match a socket and plug?
Same current, voltage, poles and PE clock. Only device type D differs (W-SCT / C-SCT / PLG).
Can an HSP1P plug be used with another Ex socket brand?
No. Use an HSP1P plug only with an HSP1P socket (mechanical interlock and coding).
What does HSP1P 16 DC50 2P PLG mate with?
Matches: HSP1P 16 DC50 2P W-SCT, HSP1P 16 DC50 2P C-SCT. Current (16 A), voltage, poles (2P) and PE position (n/a) must be identical. Other combinations do not fit mechanically.
Why has this SKU no PE position?
The 2P version has no protective earth contact. Match by current, voltage and poles.
What does 2P mean?
2P. No PE contact — in HSP1P only extra-low-voltage versions (20–25 V, 36–50 V).
Which cable and cross-section?
Cable outer diameter: M25 · 12.5–17 mm (entry range). Conductor size is set by the designer or electrician: current-carrying capacity (IEC 60364-5-52), voltage drop over the route length and automatic disconnection; in Ex areas also IEC 60079-14.
Why can a connector overheat?
Usually loose terminals (torque per instruction), undersized conductors or worn contacts. The HSP1P interlock prevents withdrawal under load. Replace an overheated connector; periodic inspection per IEC 60079-17.
Where are the documents?
HSP1P documents: EU declaration, use and maintenance instruction, catalogue.
Matching HSP1P set — 16 A · 36~50V DC · 2P · PE n/a
Matching wall / plug (and coupler when available) share current, voltage, poles, PE and AUX. The current SKU is highlighted.
| Type | SKU | Current | Voltage | Poles | PE | AUX |
|---|---|---|---|---|---|---|
| Wall socket | HSP1P 16 DC50 2P W-SCT |
16 A | 36~50V DC | 2P | n/a | None |
| Coupler socket | HSP1P 16 DC50 2P C-SCT |
16 A | 36~50V DC | 2P | n/a | None |
| Plug | HSP1P 16 DC50 2P PLG |
16 A | 36~50V DC | 2P | n/a | None |