Description
PrimeLine ATEX emergency luminaire for central battery systems. Backup power comes from a compatible central system, not from a battery inside the luminaire. Certification covers Zones 1, 2, 21 and 22. GRP body, PC diffuser, IP66/IP67. Version B: central battery without addressing. Confirm system compatibility before ordering.
- Ordering code: PL 60-2 330BRM
- Dimensions L×D×H: 670x173x107
- Power: 28 W
- Luminous flux AC: 3405 lm
- Luminous flux DC (emergency): 3405 lm
- Colour temperature: 4000 K
- CRI: >80
- IP: IP66 / IP67
- IK: IK09
- Housing: GRP
- Diffuser: Frosted (PC)
- Cable glands: M20 — 2 glands on one side and 1 on the other
- Terminals: 3-pole
- Through wiring: 2.5 mm² / 105°C insulation
- Isolating switch: yes
- Ambient temperature: -40°C…+50°C
- ATEX / IECEx: Ex II 2G Ex db eb mb IIC T4 Gb – Ex II 2D Ex tb IIIC T70°C Db
- Zone: 1
Code PL 60-2 330BRM means: 670 mm, ~12 W LED module, 3-pole terminal, M20 (2 glands on one side and 1 on the other), central battery, no addressing, with isolating switch, frosted diffuser.