Description
PL 60-1 310SRT HT is a PrimeLine luminaire, length 670 mm, power 23.4 W, Transparent diffuser. PrimeLine ATEX Zone 1 light fittings. Linear Ex LED luminaire for general lighting. Certification also covers Zones 2, 21 and 22. GRP body, PC diffuser, IP66/IP67. This SKU does not include emergency variants. HT version: ambient up to +55 °C, 220–240 V supply only.
Technical specification
| Ordering code | PL 60-1 310SRT HT |
|---|---|
| Dimensions L×D×H | 670x173x107 |
| Power | 23.4 W |
| Luminous flux AC | 2946 lm |
| Colour temperature | 4000 K |
| CRI | >80 |
| IP | IP66 / IP67 |
| IK | IK09 |
| Housing | GRP |
| Diffuser | Transparent (PC) |
| Cable glands | M20 — 1 gland, one side |
| Terminals | 3-pole |
| Through wiring | Not applicable |
| Isolating switch | yes |
| Ambient temperature | -40°C…+55°C |
| ATEX / IECEx | Ex II 2G Ex db eb mb IIC T4 Gb – Ex II 2D Ex tb IIIC T70°C Db |
| Zone | 1 |
Code PL 60-1 310SRT HT means: 670 mm, ~10 W LED module, 3-pole terminal, M20 (1 gland, one side), general lighting, with isolating switch, transparent diffuser, high-temperature HT.
Applications and limitations
- general lighting only (code S) — not internal-battery or central-battery variants;
- take photometric and Ex data from this SKU / nameplate — do not generalise the whole family;
- install per IEC 60079-14 and the instruction for the exact version (S/B, 1/3 or X/Y);
- final selection must be made by a competent person for the installation.
Documents
- ATEX certificate KSCP 25ATEX0029X
- IECEx certificate KSCP 25.0045X
- EU Declaration of Conformity — PrimeLine
- PrimeLine data sheet
- Operating instruction (SKU version)
- Photometry package
FAQ
Does this luminaire have ATEX and IECEx certificates?
Yes. PrimeLine is covered by ATEX KSCP 25ATEX0029X and IECEx KSCP 25.0045X. Take the full Ex marking and temperature from the nameplate / this SKU.
Which zones is it intended for?
Certification covers gas Zones 1 and 2 and dust Zones 21 and 22. In the shop the Zone attribute for PrimeLine is 1. Final selection depends on the installation documents.
What is the ambient temperature range?
For PL 60-1 310SRT HT: -40°C…+55°C. HT/LT suffixes change the range — always confirm in the product code.
How does general lighting differ from emergency variants?
Code S = general. Codes 1/3 = internal battery (1.5 h / 3 h). Codes B/X/Y = central battery. These are separate SKUs and category children.
Where can I download the certificate and instructions?
See Documents on this page: ATEX, IECEx, EU declaration, data sheet, version-specific instruction and photometry.
Other PrimeLine lengths / powers — General lighting · Transparent diffuser
Same function subcategory and the same terminals, gland layout and diffuser. Length and LED module vary. The current SKU is highlighted.
| SKU | Length | Module | Power | Flux AC |
|---|---|---|---|---|
PL 60-1 310SRT HT |
670 mm | 1 | 23.4 W | 2946 lm |
PL 60-2 310SRT HT |
670 mm | 2 | 28.0 W | 3613 lm |
PL 12-1 310SRT HT |
1270 mm | 1 | 43.0 W | 5979 lm |






Reviews
There are no reviews yet.