AtexBox · HSP1P
Selecting Ex sockets and plugs HSP1P
HARDO HSP1P sockets and plugs are for electrical connections in zones 1, 2, 21 and 22. Select by device type (wall W-SCT, coupler C-SCT, plug PLG), current, voltage, poles and PE clock. Certificate TÜV CY 25 ATEX 0207475 X, Ex db eb / Ex tb marking, IP66; mechanical interlock prevents withdrawal under load. Use an HSP1P plug only with an HSP1P socket. Confirm ambient temperature and cable OD on the individual SKU page.
Three device types
Pick a category, then filter by current, voltage, poles and PE.
Selection criteria
Six fields that must match on a socket–plug pair (except type code D).
- Type D
W-SCT · C-SCT (16/32 A only) · PLG
- Current
16 / 32 / 63 / 125 A
- Voltage
Catalogue ranges; IEC colour helps but does not replace the code
- Poles
2P · 3P · 4P · 5P
- PE position
IEC 60309 clock; 2P = n/a
- OC / AUX
NO contact only at 125 A (W-SCT OC / PLG OC)
16 A32 A63 A125 A W-SCTC-SCTPLG IP66Ex db ebEx tb zones 1/2/21/22IEC 60309 PE
Type comparison
| Feature | Wall W-SCT | Coupler C-SCT | Plug PLG |
|---|---|---|---|
| Currents | 16 / 32 / 63 / 125 A | 16 / 32 A only | 16 / 32 / 63 / 125 A |
| Housing material | BMC (GRP) | PA66 | PA66 |
| OC (AUX NO) | 125 A only | — | 125 A only |
| Padlockable cover | yes | per build | — |
| SKU map count | 54 | 30 | 54 |
| Current | Make / break |
|---|---|
| 16 A · 32 A | Rotate the plug in the socket (integral switch) |
| 63 A · 125 A | Rotary knob on the socket cover |
| Voltage | 3P | 4P / 5P |
|---|---|---|
| 20–25 V AC | h12 | — |
| 20–25 V DC | h10 | — |
| 36–50 V AC | h12 | — |
| 36–50 V DC | h10 | — |
| 50–250 V DC | h3 | — |
| 110–130 V AC | h4 | — |
| 200–250 V AC | h6 | h9 |
| 380–415 V AC | h9 | h6 |
| 480–500 V AC | h7 | h7 |
| 600–690 V AC | — | h5 |
2P: no PE contact. A plug only fits a socket with the same PE hour.
Selection procedure
From question to SKU in three steps.
- Type — wall, coupler or plug · or the full HSP1P category.
- Filters — current → voltage → poles → PE → (optional) AUX and cable OD.
- SKU — verify Ex, temperature, cable OD and documents; pair the other type D with the same parameters.
Warnings and limits
- Install and operate only per the HSP1P instruction and IEC 60079-14; final selection by a suitably qualified person.
- Do not mate an HSP1P plug with sockets from other Ex series.
- Do not generalise ambient temperature or cable OD across the family — values depend on current, poles and build.
- C-SCT: no 63/125 A and no OC in the catalogue.
FAQ
What certificate does HSP1P have?
ATEX TÜV CY 25 ATEX 0207475 X. Family marking: II 2G Ex db eb IIC T6…T4 Gb; II 2D Ex tb IIIC T80°C Db. Zones 1, 2, 21, 22; IP66.
How do I match a socket and plug?
Same current, voltage, poles and PE clock. Only type code D differs (W-SCT / C-SCT / PLG). IEC colour helps identify voltage but does not replace checking the ordering code.
How does switching differ between 16/32 A and 63/125 A?
16 A and 32 A: make and break by rotating the plug in the socket. 63 A and 125 A: rotary knob on the socket cover. Switch off before disconnecting per the instruction.
What does OC mean in the SKU?
Optional normally-open auxiliary contact. Catalogue range only at 125 A: W-SCT OC and PLG OC. No OC for C-SCT.
Can an HSP1P plug mate with another Ex socket?
No. An HSP1P plug must be used only with an HSP1P socket (mechanical interlock and coding).
What does the PE “clock” position (h6, h9…) mean?
On the socket face the protective earth contact sits at a set position on a clock dial (IEC 60309). The hour depends on voltage and poles, e.g. 380–415 V 4P/5P = h6, 200–250 V 4P/5P = h9. Plug and socket only mate when the PE hour is the same — a deliberate guard against connecting to the wrong voltage. Check the PE position in the SKU code and the table above.
What is the difference between 4P and 5P, and what if only 4 cores come out of the wall?
4P = 3 phases + PE (no N), 5P = 3 phases + N + PE. A three-phase load without N (e.g. a motor) uses 4P. A 5P socket needs separate N and PE: the PEN conductor is split in the distribution board, and N and PE must not be rejoined downstream. TN-C is not permitted in hazardous areas (IEC 60079-14). Connect L1, L2, L3, N, PE per the terminal marking in the HSP1P instruction.
Which cable size for a 32 A socket — 5×4 or 5×6 mm²?
The designer or electrician sizes conductors by current-carrying capacity (IEC 60364-5-52: installation method, temperature, grouping), voltage drop and automatic disconnection. On longer runs (e.g. 20–40 m) voltage drop often decides, usually leading to a larger size. In Ex areas IEC 60079-14 also applies. Cable outer diameter must fit the entry range on the SKU page.
B32 or C32 breaker? Will 32 A trip a 25 A main fuse?
Match the curve to the load: B for loads without high inrush, C for motors, compressors and welders. A 32 A breaker downstream of a 25 A main fuse is not selective — under heavy load the main fuse operates. Available power is set by the supply connection; increases are agreed with the network operator.
Is an RCD required, and which type?
General-purpose socket outlets up to 32 A need additional protection by an RCD ≤30 mA (IEC 60364-4-41). Type A or AC suits typical loads; with drives and EV charging use type B, or type A with 6 mA DC detection in the equipment (IEC 60364-7-722). The installation designer selects type and rating.
Motor runs the wrong way — what to change?
Swap any two phases (e.g. L1 and L2) with the supply isolated, in the feeder or at the load. Keep one phase sequence on all sockets on site. Work is done by an electrician; open Ex enclosures only per the HSP1P instruction.
How do I supply a 16 A or 230 V device from a 32 A socket?
A 16 A plug does not fit a 32 A socket — size, coding and PE position differ by design. In Ex areas, adapters and site distribution boxes without Ex certification are not used. Supply the smaller load from a separate HSP1P circuit with matching ratings, or via an Ex distribution board with protection sized for the load.
Can I charge an electric car from a 32 A socket?
HSP1P is an industrial connector for Ex areas, not an EV charging point. EV charging needs a circuit per IEC 60364-7-722 (dedicated circuit, RCD, DC protection). Three phases at 32 A and 400 V is about 22 kW — continuous full-current load is acceptable only if conductors, terminals and protection are rated for it.
Why does a socket or plug overheat or melt?
Usually loose terminals (torque per instruction), undersized conductors, disconnection under load or worn, dirty contacts. The HSP1P mechanical interlock prevents withdrawal under load (16/32 A: plug rotation, 63/125 A: lid knob). Replace an overheated connector; periodic inspection per IEC 60079-17.
Where are the documents?
EU declaration of conformity, use and maintenance instruction, Sockets and plugs catalogue.
Socket–plug pair configurator
Choose parameters. The tool picks the HSP1P socket and matching plug (same current, voltage, poles and PE) and adds both to the cart.