Description
HARDO HCS1P motor circuit breaker for Ex zones 1, 2, 21 and 22. Five protections (overload, short-circuit, thermal, phase loss; undervoltage optional). Large Ø 97 mm knob, operable with gloves; lockable in OFF. GRP enclosure, IP66, 440 V, AC-3 up to 25 A.
- Overload trip range: 0.4–0.63 A
- Cable glands: 3 × M25
- Undervoltage trip (U): Yes
- Auxiliary contacts 1NO+1NC: None
- ATEX: II 2 G Ex db eb IIC T4/T5/T6 Gb · II 2 D Ex tb IIIC T85°C Db
- IECEx: Ex db eb IIC T5/T6 Gb · Ex tb IIIC T85°C Db
- Zones: 1, 2 (gas) · 21, 22 (dust)
- Ambient temperature: -40°C to +55°C
- IP: IP66
- Voltage / category: 440 V · AC-3 25 A
- Rated switching capacity: 65 kA
- Dimensions (H×W×D): 250 × 260 × 160 mm
- Weight: 6.25 kg
- Main contacts: 1–10 mm² (6–10 mm² with collets)
- Auxiliary contacts: 1–2.5 mm² · AC15 1 A / 230 V
- Knob: Ø 97 mm, padlockable in OFF
Code HCS1P 252616 S01242 means: enclosure HCS1P 252616 (250 × 260 × 160 mm) · overload 0.4–0.63 A · glands 3 × M25 · option Undervoltage.