Non-armoured
Unarmoured ATEX cable glands (HARDO HCG1) are single-compression metal glands for circular unarmoured, screened or braided cables. They seal the outer sheath into an Ex enclosure. Certified ATEX/IECEx for Zones 1, 2, 21 and 22 — Ex db / Ex eb / Ex tb, IP66/IP68, −55°C … +160°C, metric M20–M90 or NPT. Separate cable strain relief is required.
To select: entry thread (metric / NPT) · cable OD A + sealing code · material · Ex marking and certificates. Not for SWA/SWB armoured cable — use Armoured (HCG2). M16 entry: HAD adaptor + HCG1 M20.
Showing 1–12 of 78 results
How to use the selection filters
The left-hand panel (on phones: the Selection button) narrows the HARDO cable-gland catalogue. Set parameters in engineering order — from cable type to diameter.
Non-armoured → HCG1 series. Armoured (SWA/SWB) → HCG2. On armoured/non-armoured child categories this filter is already fixed.
Choose metric or NPT to match the enclosure entry. Do not mix systems — thread sizes follow the selected family.
Set the thread size (e.g. M20, M25…) and material: brass, nickel-plated brass or stainless steel 316L. Multiple values are allowed — the grid shows products that match.
Overall Ø — outer cable diameter. For armoured glands also use Under sheet Ø. Only glands whose sealing range covers the value remain.
- Set cable type (or open the armoured / non-armoured subcategory).
- Match thread family to the enclosure entry (metric / NPT). M16 entry: HAD adaptor + M20 gland.
- Choose thread size and gland material.
- Enter cable OD (and under-sheet OD for HCG2 when needed).
- Click Find matching glands — the product grid updates.
- Open the SKU card and verify sealing code, Ex marking and documents.
- Above the grid, Selected specification chips appear — × removes one parameter.
- Clear in the panel resets the whole selection.
- On mobile the filter panel opens as a Bootstrap offcanvas (Selection button).
- The apply button shows how many glands match before you confirm.
- They do not replace checking the ATEX/IECEx certificate and installation instruction.
- They do not auto-add an HAD adaptor — for M16 add it separately.
- Final selection must be made by a competent person with the full installation documentation.
HCG1 — cable ranges (unarmoured)
Table for unarmoured HCG1 glands. The CODE column shows nickel-plated brass (N) examples;
the same Ø ranges and wrench sizes apply to brass (B) and stainless 316L (S) for the same sealing code.
Outer diameter of the unarmoured cable, min–max [mm].
Thread length E [mm] — entry into the enclosure.
Wrench size across flats [mm].
Dimension across corners [mm].
How to read: measure outer cable Ø → must fit column A (min–max) on the same row as the thread.
| CODE | METRIC | E [mm] | A — cable Ø [mm] | A/F | A/C | |
|---|---|---|---|---|---|---|
| min | max | |||||
| HCG1N1M20XS | M20 | 17 | 3.2 | 8.5 | 24 | 26.5 |
| HCG1N1M20S | M20 | 17 | 6.2 | 11.6 | 24 | 26.5 |
| HCG1N1M20 | M20 | 17 | 8.0 | 13.9 | 27 | 30 |
| HCG1N2M25 | M25 | 17 | 11.2 | 19.6 | 36 | 40 |
| HCG1N3M32 | M32 | 17 | 17.1 | 26.0 | 42 | 46 |
| HCG1N4M40 | M40 | 17 | 23.6 | 31.6 | 50 | 55 |
| HCG1N5M50S | M50 | 17 | 31.1 | 37.5 | 55 | 60 |
| HCG1N5M50 | M50 | 17 | 35.7 | 43.1 | 60 | 65 |
| HCG1N6M63S | M63 | 17 | 41.6 | 48.7 | 70 | 77 |
| HCG1N6M63 | M63 | 17 | 47.3 | 55.2 | 74 | 81 |
| HCG1N7M75S | M75 | 17 | 54.1 | 61.2 | 80 | 87 |
| HCG1N7M75 | M75 | 17 | 61.2 | 67.2 | 85 | 93 |
| HCG1N9M90 | M90 | 24 | 66.7 | 79.2 | 108 | 116 |
| CODE | NPT | E [mm] | A — cable Ø [mm] | A/F | A/C | |
|---|---|---|---|---|---|---|
| min | max | |||||
| HCG1N1N20XS | 1/2″ | 20 | 3.2 | 8.5 | 24 | 26.5 |
| HCG1N1N20S | 1/2″ | 20 | 6.2 | 11.6 | 24 | 26.5 |
| HCG1N1N20 | 1/2″ | 20 | 8.0 | 13.9 | 27 | 30 |
| HCG1N2N25 | 3/4″ | 21 | 11.2 | 19.6 | 36 | 40 |
| HCG1N3N32 | 1″ | 26 | 17.1 | 26.0 | 42 | 46 |
| HCG1N4N40 | 1 1/4″ | 26 | 23.6 | 31.6 | 50 | 55 |
| HCG1N5N50S | 1 1/2″ | 26 | 31.1 | 37.5 | 55 | 60 |
| HCG1N5N50 | 2″ | 27 | 35.7 | 43.1 | 61 | 65 |
| HCG1N6N63S | 2″ | 27 | 41.6 | 48.7 | 70 | 77 |
| HCG1N6N63 | 2 1/2″ | 40 | 47.3 | 55.2 | 74 | 81 |
| HCG1N7N75S | 2 1/2″ | 40 | 54.1 | 61.2 | 80 | 87 |
| HCG1N7N75 | 3″ | 42 | 61.2 | 67.2 | 91 | 93 |
| HCG1N9N90 | 3 1/2″ | 42 | 66.7 | 79.2 | 108 | 116 |
Ø ranges from HARDO pricelist / product meta. E, A/F, A/C from the HCG1 data sheet. Filter Overall Ø maps to column A.